Description
TECHNICAL DATA
MATERIAL • ENCLOSURE & BRACKET: Stainless Steel 316L
COLOUR • RED : RAL 3001 – YELLOW** : RAL1018 – BLUE** : RAL5005 – BLACK** : RAL9005
INGRESS PROTECTION • IP66/67
AMBIENT TEMPERATURE FOR OPERATION • T6 = – 40°C ~ + 55°C , T5 = – 40°C ~ + 60°C, T4 = – 40°C ~ + 70°C
CERTIFICATION • Nemko 13 ATEX 1562X, IECEX NEM 13.0032X
EX CODE • II 2 GD Ex d IIC T4 ~ T6 Gb, Ex tb IIIC T135°C ~T85°C,
STANDARD • EN / IEC 60079-0, EN / IEC 60079-1, EN / IEC 60079-31, EN 54-3
ATEX AREA ZONE • Gas zone: 1 & 2 Dust zone: 21 & 22
AMBIENT HUMIDITY* • until 95%*
POWER SUPPLY • 12-48V DC • 12-48V AC (50/60hz) • 100-240V AC (50/60hz)
RATED IMPULSE WITHSTAND VOLTAGE • 1kV following IEC 61000-4-5
CONSUMPTION • Adjustable from 5 to 25 W (factory setting 20W)
CURRENT CONSUMPTION • 0.5 to 1 A
SIGNALLING TYPE • 59 tones siren. Specific customer tones can be recorded in factory
NOISE LEVEL • Until 115 dB at 1 m
CABLES ENTRY • 2 x M20, M25**, 1/2” NPT**, 3/4” NPT** or other** (Specify)
TERMINAL • From 22 to 14 AWG – from 0.50 mm² to 2.5 mm²
NET WEIGHT • 6.2 Kg
EXTERNAL TRIGGER** • 25Hz <f<50Hz 40V<u<100V Z = 2k Ohms
* = without runoff – ** = optional – cable gland and blind plug not provided